MTL3000 series MTL3071 TEMPERATURE CONVERTER has been discontinued for sale now.
MTL3000 Series interface units offered a compact and easy-to-use means for communicating safely with process measuring, indicating, actuating and local control equipment in hazardous areas. The comprehensive range of models included analogue, switch and serial-digital signals in both directions, amplifying or otherwise conditioning them as required and at the same time providing world wide certified explosion protection for equipment and wiring in all zones and all explosive atmospheres. It also provided an alternative to the shunt-diode safety barrier where isolation was essential or preferred or a high-integrity earth was not readily available.
 
The MTL5500 Series are the recommended replacements for this series.

MTL3071 TEMPERATURE CONVERTER THC or emf input.
The MTL3071 accepts a low-level dc signal from a temperature sensor in a hazardous area, and converts it into a 4/20mA loop current in the safe area proportional to millivolts (but not temperature). It can monitor any one of six types of thermocouple, or a millivolt signal from an emf source. Calibration is carried out by the user via controls located in the top and the side of the unit. This can be effected without the use of a thermocouple since the unit's built-in cold junction compensation (CJC) is zeroed at 0°C, and can be bypassed.
Thermocouple type is switch-selectable, as is the optional safety drive which initiates either a high or low output in the event of thermocouple burnout or any cable breakage. Input zero and span are selected by switches (coarse adjustment) and potentiometers (fine adjustment).
 
 
MTL3000 series
Product CodeDescription
MTL3011   Switch/proximity detector relay - volt-free contacts
MTL3012   Switch/proximity detector relay - solid state 
MTL3013   Switch/proximity detector relay - 2-channel 
MTL3014   Switch/proximity detector relay - dual outputs
MTL3021_22  Solenoid/alarm driver ~ IIC loop powered
MTL3041   Repeater power supply - 4/20mA for 2-wire transmitters 
MTL3042   DC isolator - 4/20mA loop powered for I/P converters
MTL3043   DC isolator - 1/40mA for fire and smoke detctors
MTL3045   Isolating driver - 4/20mA for I/P converters 
MTL3046B  Repeater power supply - for ‘smart’ transmitters
MTL3052   Digital isolator - for signals up to 10kHz
MTL3054   Communications isolator/ repeater
MTL3058_59  Serial data interface ~ RS232 general purpose
MTL3071   Temperature converter ~ THC or emf input
MTL3072   Temperature converter ~ 3-wire RTD input
MTL3073   Temperature converter ~ THC or RTD input
MTL3081   Millivolt isolator - for low-level inputs
MTL3099   Dummy isolator - for terminating and isolating unused cores 
MTL3992   High stability power supply
 